  • Abstract
    The existing of the High Voltage (HV) infrastructure creates a special set of safety circumstances. Earthing system is one of the main elements to mitigate any unsafe conditions. Commissioning the earth grid certifies that the implemented system fulfills to the pertinent necessities. This paper endeavors to present vital information on how to perform the earth grid commissioning of an HV infrastructure. This paper will minutiae the minimum necessities to guarantee the test will symbolize the actual fault case that the design was based on. A flow chart diagram is established and presented in this paper to allow the determination of the most suitable injection route. The results of the multiple case studies are discussed and the results are shown in this paper.
  • Keywords
    Earth; earthing; power grids; substations; HV substation Earth grid commissioning; current injection test method; earthing system; flow chart diagram; safety circumstances; Current measurement; Earth; Electrical resistance measurement; Electrodes; Grounding; Substations; Voltage measurement; EPR; Earth Grid; Fault Current Distribution; High Voltage; OHEW; Split Factor; Transmission Mains;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics and Applications (ICIEA), 2013 8th IEEE Conference on
  • Conference_Location
    Melbourne, VIC
  • Print_ISBN
    978-1-4673-6320-4
  • Type

    conf

  • DOI
    10.1109/ICIEA.2013.6566342
  • Filename
    6566342