DocumentCode :
639688
Title :
Effects of MV PILC cables ageing process on the diagnostic parameters: P-factor and tanδ
Author :
Mladenovic, I. ; Weindl, Christian ; Scharrer, Thomas
Author_Institution :
Dept. of Electr. Energy Syst., Univ. of Erlangen-Nuremberg, Erlangen, Germany
fYear :
2013
fDate :
June 30 2013-July 4 2013
Firstpage :
92
Lastpage :
95
Abstract :
During field operation, power equipment is exposed to numerous impacts (especially thermal and electrical stress), which result in a continuous deterioration of its insulation material. The grade of the deterioration can be weighted by different diagnostic measurements. Within an accelerated ageing experiment on paper insulated lead covered (PILC) cables, several diagnostic parameters have been measured regularly during the ageing process of ca. 2 years. The cable samples are PILC cables (20 kV, 150 mm2) of 13 m length, which are differently pre-aged (from brand new, up to cables that have been in operation for 60 years). In this article aging effects of this insulation system on dissipation factor and parameters of return voltage curve as well as on p-factor will be shown and discussed.
Keywords :
ageing; cable insulation; paper; MV PILC cables ageing process; diagnostic parameters; dissipation factor; electrical stress; insulation material; paper insulated lead covered cables; return voltage curve; thermal stress; Aging; Cable insulation; Dielectrics; Temperature; Temperature measurement; Voltage measurement; PILC cable; ageing; diagnostics; dissipation factor; medium voltage cable; return voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Solid Dielectrics (ICSD), 2013 IEEE International Conference on
Conference_Location :
Bologna
ISSN :
2159-1687
Print_ISBN :
978-1-4799-0807-3
Type :
conf
DOI :
10.1109/ICSD.2013.6619700
Filename :
6619700
Link To Document :