• DocumentCode
    645807
  • Title

    Multi-agent system based voltage regulation in a low-voltage distribution network

  • Author

    Lang, Shinan ; Niannian Cai ; Mitra, Joydeep

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Michigan State Univ., East Lansing, MI, USA
  • fYear
    2013
  • fDate
    22-24 Sept. 2013
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Due to the high feed of regenerative power in many low-voltage distribution networks, it is possible that in some nodes inadmissible voltages appear. This paper presents a way to comply with the prescribed voltage band. It is realized by a multiagent system, which executes a three-stage algorithm to adjust the voltage at the nodes of the grid. A possible configuration is presented with a voltage regulated distribution transformer. It regulates the secondary voltage in several steps. The multi-agent system measures the voltages in different points in a network. The three-step algorithm controls the voltage, reactive and real power to comply with the prescribed voltage band. The paper shows a flexible communication structure, which is used by the agents to exchange data. An example network is presented. This displays the effectiveness of the communication cycle. Furthermore, the influence of the three-step algorithm is shown in a test system.
  • Keywords
    distribution networks; multi-agent systems; power grids; voltage control; flexible communication structure; grid nodes; low-voltage distribution network; multiagent system; real power; three-stage algorithm; voltage controls; voltage regulated distribution transformer; voltage regulation; Actuators; Generators; Multi-agent systems; Reactive power; Renewable energy sources; Voltage control; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    North American Power Symposium (NAPS), 2013
  • Conference_Location
    Manhattan, KS
  • Type

    conf

  • DOI
    10.1109/NAPS.2013.6666960
  • Filename
    6666960