DocumentCode :
647617
Title :
Wind turbines voltage support in weak grids
Author :
Sulla, Francesco ; Svensson, Jorgen ; Samuelsson, Olof
Author_Institution :
Lund Univ., Lund, Sweden
fYear :
2013
fDate :
21-25 July 2013
Firstpage :
1
Lastpage :
5
Abstract :
This paper investigates how Full-Scale Converter (FSC) wind turbines can contribute to voltage support in weak grids. A novel voltage support strategy is proposed, which optimizes the voltage support during the fault. This strategy is compared to the voltage support required by two grid codes, the Danish and the German E.ON ones. The influence of a number of parameters, as the network X/R ratio, the voltage support controller gain and the post-fault power ramp is investigated. A sensitivity analysis with regard to uncertainties in the knowledge of the X/R ratio is performed. Finally, the voltage support provided by a wind power plant (WPP) is compared to that provided by a conventional power plant with synchronous generation. Simulation results indicate that a FSC WPP if properly controlled is able to provide a post-fault voltage support comparable to the one provided by a synchronous generator.
Keywords :
power generation control; power generation faults; power grids; synchronous generators; voltage control; wind turbines; Danish code; FSC; German E.ON code; X/R ratio; full-scale converter; post-fault power ramp; synchronous generator; voltage support controller gain; voltage support strategy; weak grids; wind power plant; wind turbines; Impedance; Power capacitors; Reactive power; Synchronous generators; Voltage control; Wind turbines; Wind turbines; voltage support; weak grid;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting (PES), 2013 IEEE
Conference_Location :
Vancouver, BC
ISSN :
1944-9925
Type :
conf
DOI :
10.1109/PESMG.2013.6672130
Filename :
6672130
Link To Document :
بازگشت