• DocumentCode
    647765
  • Title

    Phasor measurement and CT saturation compensation through embedding

  • Author

    Ji, T.Y. ; Li, M.S. ; Wu, Q.H.

  • Author_Institution
    Sch. of Electr. Power, South China Univ. of Technol. (SCUT), Guangzhou, China
  • fYear
    2013
  • fDate
    21-25 July 2013
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Phasor measurement measures the amplitude and phase angle of the signal to determine the health of the power system. If a fault occurs on a transmission line, the input current of a relay may contain harmonics and exponentially decaying DC offset. This paper proposes an embedding-based scheme, which transfers a power system signal to the phase space according to its mathematical properties, to first remove the DC offset then measure the amplitude and phase angle of the fundamental component of the fault signal. The idea of embedding is also engaged to compensate the saturations of a secondary current, using the information provided by the unsaturated portion.
  • Keywords
    current transformers; phase space methods; phasor measurement; CT saturation compensation; DC offset; amplitude measurement; current transformer; embedding based scheme; mathematical property; phase angle measurement; phase space; phasor measurement; power system signal; relay input current; transmission line; Circuit faults; Current measurement; Estimation; Fault currents; Power measurement; Power systems; Transmission line measurements; CT saturation; Delay coordinate embedding; phasor measurement; power system;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting (PES), 2013 IEEE
  • Conference_Location
    Vancouver, BC
  • ISSN
    1944-9925
  • Type

    conf

  • DOI
    10.1109/PESMG.2013.6672296
  • Filename
    6672296