• DocumentCode
    647797
  • Title

    Energization study of five-terminal multi-level HVDC converter station

  • Author

    Singh, Neeraj Kumar ; Carlsson, Jonas X.

  • Author_Institution
    Grid Syst. at the ABB UK Ltd., Stone, UK
  • fYear
    2013
  • fDate
    21-25 July 2013
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Impact of HVDC converter energization connected to muti-terminal hub on network performance is presented in this paper. Due to capacitors used in HVDC converter, its energization produces a higher inrush current causing a severe voltage dip in both the ac and dc systems potentially exceeding the allowable limits. Similarly dc cable and HVDC transformer energization also causes a higher inrush current that can damage the semiconductor devices used in the converter system. The paper discusses fundamental principles, energization schemes and pre-insertion resistors as a mitigation measure among other. A case study was selected and the results are presented under various grid-conditions.
  • Keywords
    HVDC power convertors; power grids; power transformers; resistors; AC systems; DC cable energization; DC systems; HVDC transformer energization; energization study; five-terminal multilevel HVDC converter station; grid-conditions; inrush current; mitigation measure; mutiterminal hub; network performance; preinsertion resistors; semiconductor devices; voltage dip; Circuit breakers; Circuit faults; HVDC transmission; Surges; Switches; Transient analysis; Voltage fluctuations; Energization; HVDC; Insulation Coordination study;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting (PES), 2013 IEEE
  • Conference_Location
    Vancouver, BC
  • ISSN
    1944-9925
  • Type

    conf

  • DOI
    10.1109/PESMG.2013.6672333
  • Filename