Transient overvoltage rating and BIL of the transformerless intelligent power substation
Author
Carr, Jerry ; Zhenyuan Wang ; Bhattacharya, Surya ; Patel, Dinesh
Author_Institution
ABB Corp. Res. Center, Raleigh, NC, USA
fYear
2013
fDate
21-25 July 2013
Firstpage
1
Lastpage
5
Abstract
The overvoltage impulse protection of the transformerless intelligent power substation (TIPS) is explored in this paper. Two failure mechanisms, excess current causing thermal failure of the devices and excess component to ground voltage causing failure of the insulation, are considered. A variety of grounding, protection, and filter circuits were analyzed. It was found that the current and voltage do not exceed the limits of safety if the midpoint of the TIPS DC bus capacitor bank is grounded. A recommended protection scheme was proposed based on these results, consisting of a MOV at the input to the TIPS to divert surge currents and a reactive connection to ground to limit the device currents without resulting in a large voltage between the midpoint and ground. A large voltage was found to fall across the input filter, which should be designed with sufficient BIL to withstand this voltage.
Keywords
earthing; electrical safety; insulation; overvoltage protection; substation protection; BIL; TIPS DC bus capacitor bank; basic insulation level; excess current causing thermal failure; failure mechanism; filter circuit; ground voltage; grounding circuit; insulation failure; overvoltage impulse protection; protection circuit; safety limit; transformerless intelligent power substation; transient overvoltage rating; lightning; overvoltage protection; power electronics transformer; solid state transformer;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting (PES), 2013 IEEE
Conference_Location
Vancouver, BC
ISSN
1944-9925
Type
conf
DOI
10.1109/PESMG.2013.6672424
Filename
6672424
Link To Document