• DocumentCode
    648109
  • Title

    Control strategy for 2-terminal high power LCL DC-DC converter

  • Author

    Weixing Lin ; Jovcic, Dragan

  • Author_Institution
    Sch. of Eng., Univ. of Aberdeen, Aberdeen, UK
  • fYear
    2013
  • fDate
    21-25 July 2013
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper proposes a control strategy for 2-terminal LCL DC-DC converter. Cascaded control consists of outer loop power control, with inner loop current control in order limit converter currents. Three coordinate frames are used in order to satisfy zero reactive current at each bridge and power balance. The control strategy enables the 2-terminal LCL DC-DC converter operating in the whole range of the designed power rating and current limitation during faults. Operating principles of the LCL DC-DC converter and procedures for design the control strategy are presented. Effectiveness of the control strategy during step power orders and DC faults is verified by simulation of a detailed PSCAD model for a 200kV/640kV, 500MW 2-terminal LCL DC-DC converter.
  • Keywords
    DC-DC power convertors; electric current control; power control; cascaded control; control strategy; high power LCL DC DC converter; inner loop current control; outer loop power control; power 500 MW; power balance; voltage 200 kV; voltage 640 kV; zero reactive current; Bridge circuits; Circuit faults; Educational institutions; Equations; Reactive power; Topology; Voltage control; DC grids; DC-DC power conversion; IGBT converter; current control; high voltage DC transmission;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting (PES), 2013 IEEE
  • Conference_Location
    Vancouver, BC
  • ISSN
    1944-9925
  • Type

    conf

  • DOI
    10.1109/PESMG.2013.6672677
  • Filename
    6672677