Title :
Solar photovoltaic inverters transient over-voltages
Author :
Bravo, Richard J. ; Salas, Rodolfo ; Yinger, Robert ; Robles, Steven
Author_Institution :
Southern California Edison, Rosemead, CA, USA
Abstract :
This paper presents solar photovoltaic (SPV) inverters test results performed in Southern California Edison´s (SCE) Distributed Energy Resources (DER) laboratory. The lab´s engineers tested a variety of commercial three-phase solar PV inverters from different manufacturers and began performing commissioning tests on commercial SPV installations interconnected directly on SCE´s distribution circuits. The primary objective of these load rejection tests is to assess transient over-voltages (TOV) created when SPV inverters are disconnected from the grid and injecting electrical power to the grid (load rejection). The data acquired in this project will support the updates to existing standards. The key results presented are associated with TOV generated by SPV inverters during grid disconnection.
Keywords :
invertors; overvoltage; photovoltaic power systems; power grids; solar power stations; Southern California Edison; distributed generation; electrical power injection; grid disconnection; load rejection test; solar photovoltaic inverter; three-phase solar PV inverter; transient over-voltage; Integrated circuit interconnections; Inverters; Photovoltaic systems; Software; Standards; Testing; Transient analysis; SPV inverters; converters; distributed generation; electronics coupled generation; solar PV plants; solar photovoltaic; solar photovoltaic inverters; transient over-voltage;
Conference_Titel :
Power and Energy Society General Meeting (PES), 2013 IEEE
Conference_Location :
Vancouver, BC
DOI :
10.1109/PESMG.2013.6672980