DocumentCode :
648486
Title :
Modelling considerations for the Hydro One real-time GMD management system
Author :
Marti, L. ; Rezaei-Zare, Afshin ; Yan, An
Author_Institution :
Hydro One Networks Inc., Toronto, ON, Canada
fYear :
2013
fDate :
21-25 July 2013
Firstpage :
1
Lastpage :
6
Abstract :
Hydro One (Ontario, Canada) has implemented a Geomagnetic Disturbances (GMD) management system in its control centre that combines real-time tracking of GMD events as well as an assessment of Geomagnetically Induced Currents (GIC) on every circuit and transformer in the 230 kV and 500 kV networks from magnetic field measurements. Transformer reactive power loss and hot spot heating due to half-cycle saturation of every transformer with a grounded winding above 230 kV is also estimated. The computational demands in real time required modeling techniques not usually associated with GIC simulations in large networks. This paper describes the modeling approach, capabilities, and usage to make real-time operational decisions during a GMD event.
Keywords :
geomagnetism; hydroelectric power stations; magnetic field measurement; power system simulation; power transformers; GIC; GMD events; Hydro One real-time GMD management system; control centre; geomagnetic disturbances; geomagnetically induced currents; grounded winding; half-cycle saturation; hot spot heating; magnetic field measurements; real-time tracking; transformer reactive power loss; Circuit faults; Harmonic analysis; Magnetic field measurement; Phase transformers; Reactive power; Real-time systems; Temperature measurement; GIC; Geomagnetism; Power System Modelling;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting (PES), 2013 IEEE
Conference_Location :
Vancouver, BC
ISSN :
1944-9925
Type :
conf
DOI :
10.1109/PESMG.2013.6673069
Filename :
6673069
Link To Document :