DocumentCode
650228
Title
Contingency analysis on 500kV Jawa-Bali Transmission Line System based on Power Load Performance Index
Author
Putranto, Lesnanto Multa ; Perdana, Julian Widya ; Isnaeni, M.
Author_Institution
Dept. of Electr. Eng. & Inf. Technol., UGM, Yogyakarta, Indonesia
fYear
2013
fDate
7-8 Oct. 2013
Firstpage
332
Lastpage
336
Abstract
The line outage of a power system may cause overloads on the lines, overvoltage on buses, and undervoltage on buses that can threat the power system security itself. The effect of the contingency of each power system element is vary. Power Load Performance Indexes as one of the contingency indexes can be implemented to rank the contingency level of each power system lines. N-1 contingency line is applied at 500 kV Jawa Bali Transmission System to rank the severe of contingency and to evaluate the effect of contingency of each element. Tanjung Jati-Ungaran line has the biggest contingency index which means it would be the worst scenario of the line outage.
Keywords
power system reliability; power system security; power transmission planning; power transmission protection; Jawa-Bali transmission line system; Tanjung Jati-Ungaran line; contingency analysis; line outage; power load performance index; power system line; power system security; voltage 500 kV; Contingency; Power Load Performance Indexes; Power System Security;
fLanguage
English
Publisher
ieee
Conference_Titel
Information Technology and Electrical Engineering (ICITEE), 2013 International Conference on
Conference_Location
Yogyakarta
Print_ISBN
978-1-4799-0423-5
Type
conf
DOI
10.1109/ICITEED.2013.6676263
Filename
6676263
Link To Document