• DocumentCode
    653684
  • Title

    Anatomy of a complex electrical failure and its forensics analysis

  • Author

    Mardegan, Claudio S. ; Shipp, David

  • fYear
    2013
  • fDate
    6-11 Oct. 2013
  • Firstpage
    1
  • Lastpage
    10
  • Abstract
    This paper depicts an accident that happened in 2010 in a Brazilian Chemical Plant. A combination of different events, installations and commissioning errors coupled with equipment failures involving the primary substation, resulted in catastrophic failure. A single phase failure of a 138 kV disconnect switch, during closing, initiated events and phenomena that resulted in a complete plant shut down. This paper will walk the reader thru the events, forensics analysis as well as power system analysis that allowed the authors to identify what happened, how it happened and what to do to prevent it from happening again. The paper will show how the anatomy of the problem, involving equipment failure, single phase arcing, switching transients, overvoltage, capacitive coupling, transferred surge voltages, ungrounded system, transient overvoltage due to an arcing ground fault on an ungrounded system, insulation coordination, flash-over and lack of adequate surge protection. All of which resulted in a catastrophic failure of an arc resistant switchgear and a serious arc flash incident. The research followed some steps that will be commented here as well as the lessons learned.
  • Keywords
    arcs (electric); earthing; electrical accidents; failure analysis; flashover; overvoltage protection; power apparatus; power system protection; substation protection; surge protection; switching transients; accident; arc flash incident; arc resistant switchgear; arcing ground fault; capacitive coupling; catastrophic failure; complex electrical failure; disconnect switch; equipment failure; flashover; forensics analysis; installations and commissioning error; insulation coordination; power system analysis; substation; surge protection; switching transient; transferred surge voltage; transient overvoltage; ungrounded system; voltage 138 kV; Capacitance; Electric machines; Failure analysis; Switchgear; Voltage control; Arc Flash; flash-over; forensics; grounding; grounding monitoring; overvoltage; power system analysis; power system design; protection; surge protection; switching transient; transferred surge; transient overvoltage; ungrounded system;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting, 2013 IEEE
  • Conference_Location
    Lake Buena Vista, FL
  • ISSN
    0197-2618
  • Type

    conf

  • DOI
    10.1109/IAS.2013.6682593
  • Filename
    6682593