DocumentCode :
665401
Title :
Wide area measurement based adaptive zone-2 setting for multiterminal lines
Author :
Naidu, O.D. ; Pradhan, A.K.
Author_Institution :
Corp. Res. Center, Grid Autom. Res., ABB, Bangalore, India
fYear :
2013
fDate :
10-13 Nov. 2013
Firstpage :
1
Lastpage :
5
Abstract :
This paper presents adaptive zone-2 distance relay characteristics for multi-terminal power transmission system using PMU data. The apparent impedance equation which includes the infeed, outfeed and line shunt capacitance of the multi-terminal system is derived. For a 400 kV multi-terminal system, the results indicate that the trip boundary is significantly changing with the operating conditions. An adaptive setting method using Phasor Measurement Unit (PMUs) data is proposed and tested using simulated data obtained through EMTDC-PSCAD.
Keywords :
phasor measurement; power transmission lines; EMTDC-PSCAD; PMU data; adaptive zone-2 distance relay characteristics; apparent impedance equation; infeed shunt capacitance; line shunt capacitance; multiterminal power transmission line system; outfeed capacitance; phasor measurement unit; trip boundary; voltage 400 kV; wide area measurement; Adaptive systems; Circuit faults; Impedance; Phasor measurement units; Power systems; Protective relaying; Adaptive Protection; Apparent Impedance and Phasor Measurement Unit; Distance Protection; Power Systems; Zone-2 Setting;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Innovative Smart Grid Technologies - Asia (ISGT Asia), 2013 IEEE
Conference_Location :
Bangalore
Print_ISBN :
978-1-4799-1346-6
Type :
conf
DOI :
10.1109/ISGT-Asia.2013.6698727
Filename :
6698727
Link To Document :