• DocumentCode
    665798
  • Title

    Analysis of VSC-based HVDC system under DC faults

  • Author

    Rafferty, Joseph ; Morrow, D. John ; Xu, Lie

  • Author_Institution
    Sch. of Electron., Electr. Eng. & Comput. Sci., Queen´s Univ. Belfast, Belfast, UK
  • fYear
    2013
  • fDate
    10-13 Nov. 2013
  • Firstpage
    459
  • Lastpage
    464
  • Abstract
    This paper analyzes the behavior of a Voltage Source Converter Based HVDC system under DC cable fault conditions. The behavior of the HVDC system during a permanent line-to-earth fault is analyzed, outlining the systems configuration and behavior at each stage of the fault timeline. Operation of the proposed system under a single earthing configurations, i.e. Converter (solid) earthed/AC transformer unearthed, was analyzed and simulated, with particular attention paid to the converters operation. It was observed that the development of potential earth loops within the system as a result of DC line-to-earth faults leads to substantial overcurrent and results in system configuration oscillation.
  • Keywords
    HVDC power convertors; HVDC power transmission; earthing; power cables; power transmission faults; DC cable fault conditions; VSC-based HVDC system analysis; converter earthed-AC transformer unearthed analysis; fault timeline; permanent line-to-earth fault analysis; potential earth loops; single earthing configurations; system configuration oscillation; voltage source converter; Cable insulation; Capacitors; Circuit faults; Grounding; Oscillators; Power conversion; DC Fault; HVDC; VSC; Wind Integration;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics Society, IECON 2013 - 39th Annual Conference of the IEEE
  • Conference_Location
    Vienna
  • ISSN
    1553-572X
  • Type

    conf

  • DOI
    10.1109/IECON.2013.6699179
  • Filename
    6699179