• DocumentCode
    66813
  • Title

    A Novel Approach to Utilize PLC to Detect Corroded and Eroded Segments of Power Transmission Lines

  • Author

    Hamidi, R. Jalilzadeh ; Hosseinian, Seyed Hossein ; Sadeghi, Seyed Hossein Hesamedin ; Zhihua Qu

  • Author_Institution
    Electr. Eng. Dept., Amirkabir Univ. of Technol., Tehran, Iran
  • Volume
    30
  • Issue
    2
  • fYear
    2015
  • fDate
    Apr-15
  • Firstpage
    746
  • Lastpage
    754
  • Abstract
    A great number of existing power transmission lines have aged throughout the world. A considerable proportion of them are located in the environments that exacerbate their corrosion and erosion process. In-time detection of defects necessitates the use of nondestructive testing (NDT) techniques. Scanning the lines with robots and helicopters are the methods in use. In this paper, we propose a new NDT technique that uses the elements of power-line carriers, generally for information communication purposes, to detect the possibly corroded and eroded segments of each phase along a transmission line. The proposed NDT technique is based on the backward-wave propagation produced by a change in the characteristic impedance of a power transmission line, resulting from corrosion and erosion. To demonstrate the viability of the proposed approach, “EMTPWorks” is used to perform simulations. It is shown that the proposed technique can locate the surface defects and estimate the severity of them in transmission line conductors.
  • Keywords
    conductors (electric); corrosion; helicopters; nondestructive testing; power cables; power transmission lines; robots; EMTPWorks; NDT technique; PLC Utilization; backward-wave propagation; characteristic impedance; corrosion segment detection process; defect in-time detection; erosion segment detection process; helicopters; information communication purposes; line scanning; nondestructive testing techniques; power transmission line conductors; power-line carrier elements; robots; surface defect location; Conductivity; Conductors; Corrosion; Couplings; Impedance; Poles and towers; Power transmission lines; Conductor aging; corrosion; erosion; nondestructive testing (NDT); power-line carrier (PLC);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2014.2326167
  • Filename
    7042362