DocumentCode :
66977
Title :
Half-Interval Method Applied in Feeder Terminal Unit Overcurrent Detecting Curve Setting
Author :
Chao-Rong Chen ; Chi-Juin Chang
Author_Institution :
Electr. Eng. Dept., Nat. Taipei Univ. of Technol., Taipei, Taiwan
Volume :
30
Issue :
4
fYear :
2015
fDate :
Aug. 2015
Firstpage :
1898
Lastpage :
1905
Abstract :
Currently, self-healing is one of the most important functions in the smart grid. Meanwhile, fault detection, isolation, and restoration of feeder automation systems dominate the self-healing function in power distribution systems. The steps of the aforementioned function depend on the fault flag status of the feeder terminal unit. The conditions for setting this flag are judged by the feeder terminal unit overcurrent detecting curve. This paper found an efficient approach to calculate this curve via a half-interval method. Versatile application software with the curve plotting capability was also developed and deployed on the web server of the information-management department of Taiwan Power Company and is running successfully.
Keywords :
distribution networks; information management; power system management; smart power grids; Taiwan Power Company; feeder automation systems; feeder terminal unit overcurrent detecting curve setting; half-interval method; information-management department; power distribution systems; self-healing function; smart grid; web server; Circuit faults; Fault currents; Fuses; Power distribution; Relays; Smart grids; Upper bound; Computer aided analysis; IEEE standards; fault currents; piecewise linear approximation; power distribution protection;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2014.2375878
Filename :
6971227
Link To Document :
بازگشت