    Investigation of SSR risk in Akkuyu NEPP

  • Author

    Tanidir, Ozgur ; Cebeci, M. Erkut

  • Author_Institution
    TUBITAK MAM Energy Inst., Ankara, Turkey
  • fYear
    2013
  • fDate
    28-30 Nov. 2013
  • Firstpage
    200
  • Lastpage
    204
  • Abstract
    Subsynchronous Resonance (SSR) is the build-up of electrical and mechanical vibrations in power system as a result of interactions and energy interchanges between a turbine generator set and the rest of the power system which leads to significant shaft damages In general, power plants close to the series compensation may prone to several subsynchronous interactions, hence the risk analysis studies should be conducted to prevent possible hazardous effects. In this paper, SSR risk for Akkuyu NEPP which will be built in the southern region of Turkey close to series compensated transmission lines is investigated. The paper first provides brief information related to SSR phenomenon, types of SSR and techniques to analyze phenomenon. After, SSR study methodology for Akkuyu NEPP case and results are presented. Results of this study have revealed that there will be no SSR risk exists for planned network connection of Akkuyu NEPP.
  • Keywords
    nuclear power stations; power system stability; power transmission lines; risk analysis; subsynchronous resonance; turbogenerators; Akkuyu NEPP; SSR risk analysis; Turkey; electrical vibrations; mechanical vibrations; nuclear electric power plant; power plants; power system; series compensated transmission lines; subsynchronous interactions; subsynchronous resonance; turbine generator; Damping; Generators; Oscillators; Resonant frequency; Shafts; Torque; Turbines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical and Electronics Engineering (ELECO), 2013 8th International Conference on
  • Conference_Location
    Bursa
  • Print_ISBN
    978-605-01-0504-9
  • Type

    conf

  • DOI
    10.1109/ELECO.2013.6713831
  • Filename
    6713831