DocumentCode :
674792
Title :
Modified parallel resonance type Fault Current Limiter
Author :
Farsadi, Murtaza ; Dizaji, Tohid Sattarpur ; Kakesoury, Bijan
Author_Institution :
Urmia Univ., Urmia, Iran
fYear :
2013
fDate :
28-30 Nov. 2013
Firstpage :
248
Lastpage :
252
Abstract :
In this paper a new parallel resonance Fault Current Limiter (FCL) has been modified in a way that can sustain the magnitude of fault current and control it in a desired value. The operation is based on using parallel L&C resonance circuit with a resistor that reduces transient time and a pair of thyristors for controlling the value of fault current. Injected impedance can be controlled by changing firing angles of thyristors. Simulation with PSCAD/EMTDC software shows effectiveness of this topology for controlling fault current.
Keywords :
electric current control; fault current limiters; PSCAD-EMTDC software; fault current control; fault current magnitude; impedance control; modified parallel resonance-type fault current limiter; parallel L&C resonance circuit; parallel resonance FCL; thyristor firing angles; thyristors; transient time reductionm; Circuit faults; Fault current limiters; Fault currents; Impedance; Inductors; Power systems; Thyristors;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical and Electronics Engineering (ELECO), 2013 8th International Conference on
Conference_Location :
Bursa
Print_ISBN :
978-605-01-0504-9
Type :
conf
DOI :
10.1109/ELECO.2013.6713841
Filename :
6713841
Link To Document :
بازگشت