DocumentCode :
676536
Title :
DC fault analysis of MMC based HVDC system for large offshore wind farm integration
Author :
Yang Gao ; Bazargan, Masoud ; Lie Xu ; Wuxing Liang
Author_Institution :
Sch. of Electron., Electr. Eng. & Comput. Sci., Queen´s Univ. of Belfast, Belfast, UK
fYear :
2013
fDate :
9-11 Sept. 2013
Firstpage :
1
Lastpage :
4
Abstract :
This paper analyzes the behaviour of a modular multilevel converter (MMC) based HVDC system under DC cable fault conditions. The behaviour of the HVDC system during a permanent line-to-line fault is analyzed in details at each stage of the fault timeline. Operation of the proposed system under a specific earthing configuration i.e. converter unearthed /AC transformer secondary side and DC cable solidly earthed, is also analyzed. Simulation studies are provided to assist the analytical analysis. It is observed that both faults leads to substantial AC and DC over-current and result in DC side oscillations.
Keywords :
HVDC power transmission; earthing; power convertors; power transmission faults; wind power plants; AC over-current; AC transformer secondary side; DC cable fault conditions; DC cable solidly earthed; DC fault analysis; DC over-current; DC side oscillations; MMC based HVDC system; earthing configuration; large offshore wind farm integration; modular multilevel converter; DC fault; HVDC; MMC; wind farm;
fLanguage :
English