• DocumentCode
    678272
  • Title

    Equivalent circuit model of cascade connected partial core resonant transformers

  • Author

    Irani, Yanosh ; Lapthorn, Andrew ; Bodger, Pat

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Canterbury, Christchurch, New Zealand
  • fYear
    2013
  • fDate
    Sept. 29 2013-Oct. 3 2013
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper presents a proof of concept and equivalent circuit analysis of a cascade arrangement of tunable HV testing transformers intended for field use. The transformers use a partial core with air completing the flux path and are tuned to resonate with insulation capacitance. This minimises the power drawn from the supply and the size and weight of the transformer. A prototype set of transformers were built to validate the model. Each transformer was modelled as a set of coupled inductors to determine the input impedance frequency response. Good agreement is shown between the modelled and measured input impedance. The inclusion of core loss resistance was shown to significantly increase the accuracy of the cascade model.
  • Keywords
    equivalent circuits; frequency response; power inductors; power supply quality; power transformer testing; transformer insulation; HV testing transformers; cascade arrangement; cascade connected partial core; core loss resistance; coupled inductors; equivalent circuit; frequency response; insulation capacitance; power supply; resonant transformers; IEEE Xplore; Integrated circuits; Polymers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Conference (AUPEC), 2013 Australasian Universities
  • Conference_Location
    Hobart, TAS
  • Type

    conf

  • DOI
    10.1109/AUPEC.2013.6725432
  • Filename
    6725432