DocumentCode
684171
Title
Anti-icing performances of super hydrophobic insulator
Author
Yong Li ; Yuan Wei ; Qian Wang ; Gaolin Wu ; Jin Fu ; Jian Li ; Zhengyong Huang ; Yonglong Yan
Author_Institution
Electr. Power Res. Inst., Chongqing Electr. Power Co., Chongqing, China
fYear
2013
fDate
20-23 Oct. 2013
Firstpage
438
Lastpage
443
Abstract
Icing on transmission line threats to the safe operation of power grid. At present widely used coatings including RTV coating have the hydrophobic property whose contact angle is about 110° and cannot have good anti-icing effect. Here super-hydrophobic surface whose contact angle is about 150° and contact angle hysteresis less than 5° is prepared and its anti-icing characteristic is detected. The leakage current test in time-domain and frequency-domain, ultraviolet imaging test and AC icing flashover voltage test are adopted. Results show that compared with RTV coating, the super-hydrophobic surface owns less leakage current, fewer ultraviolet photons and higher AC flashover voltage which shows great application potential of super-hydrophobic surface in external insulation field.
Keywords
coatings; contact angle; flashover; hydrophobicity; insulators; power transmission lines; AC icing flashover voltage test; RTV coating; antiicing characteristic; antiicing effect; antiicing performances; contact angle; contact angle hysteresis; external insulation field; frequency-domain; hydrophobic property; power grid; super hydrophobic insulator; super-hydrophobic surface; time-domain; transmission line threats; ultraviolet imaging test; ultraviolet photons; Coatings; Flashover; Glass; Insulators; Leakage currents; Photonics; Substrates; RTV; flashover voltage; leakage current; super-hydrophobic surface; ultraviolet image;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
Conference_Location
Shenzhen
Type
conf
DOI
10.1109/CEIDP.2013.6748260