DocumentCode :
684205
Title :
Preliminary study of bubble formation in vegetable oil filled power transformer
Author :
Perkasa, Caesar Y. ; Wijaya, Jaury ; Lelekakis, Nick ; Martin, Daniel
Author_Institution :
Centre for Power Transformer Monitoring, Diagnostics, & Life Manage., Monash Univ., Clayton, VIC, Australia
fYear :
2013
fDate :
20-23 Oct. 2013
Firstpage :
551
Lastpage :
554
Abstract :
This paper presents the work performed to date on investigating water bubble formation in transformer oil and cellulose insulation systems, and any impact that using a vegetable oil dielectric will have in contrast to standard mineral oil. It is important to understand this phenomenon because it can lead to the failure of a transformer on overload, when water suddenly migrates from the cellulose into the oil. The system used to investigate bubbling is presented in this paper along with a discussion on how bubbling occurs. The next step will be to re-perform this investigation using vegetable oil under a variety of different conditions.
Keywords :
bubbles; power transformer insulation; transformer oil; vegetable oils; water; cellulose insulation systems; mineral oil; power transformer; transformer oil; vegetable oil; water bubble formation; Mathematical model; Minerals; Oil insulation; Power transformer insulation; Windings;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
Conference_Location :
Shenzhen
Type :
conf
DOI :
10.1109/CEIDP.2013.6748294
Filename :
6748294
Link To Document :