  • Title

    A fast method of voltage stability margin load for limit induced bifurcation

  • Author

    Yao Dan ; Zhong Hao

  • Author_Institution
    Sch. of Electr. Eng. & Renewable Energy, China Three Gorges Univ., Yichang, China
  • fYear
    2013
  • fDate
    8-11 Dec. 2013
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Limit induced bifurcation (LIB) of power system is usually caused by reactive power output of generators exceeds the limit. According to this feature, a fast calculation method for voltage stability load margin of limit induced bifurcation is presented. The algorithm establishes the load margin solving model of limit induced bifurcation for power system voltage stability; considering the constraints of the reactive power output of generators, the load increment step can be determined based on local curve fitting technology; then, combined with step binary search method, it is easy to find the limit induced bifurcation point of power system. The effectiveness of the proposed method is demonstrated through IEEE-118 bus systems.
  • Keywords
    bifurcation; electric generators; power system stability; reactive power; IEEE -118 bus systems; LIB; binary search method; limit induced bifurcation; local curve fitting technology; power system voltage stability; reactive power output; voltage stability load margin; Generators; Load flow; Mathematical model; Power system stability; Reactive power; Stability criteria; Limit induced bifurcation; Load margin; Local curve fitting; Sensitivity; Voltage stability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2013 IEEE PES Asia-Pacific
  • Conference_Location
    Kowloon
  • Type

    conf

  • DOI
    10.1109/APPEEC.2013.6837316
  • Filename
    6837316