DocumentCode
690812
Title
Experience with Partial Discharge detection at high voltage Gas Insulated Switchgear by ultra high frequency (UHF) method
Author
Chan, L.K. ; So, K.L. ; Chow, KIN KEE
Author_Institution
CLP Power Hong Kong Ltd., Hong Kong, China
fYear
2013
fDate
8-11 Dec. 2013
Firstpage
1
Lastpage
4
Abstract
The paper reviews the experience of Partial Discharge (PD) detection at 400kV and 132kV Gas Insulated Switchgear (GIS) by UHF method. It outlines the principle of UHF signal emission from possible PD inside HV GIS and relevant detection methods applied. Two real cases with detected incipient fault modes at 400kV and 132kV GIS are being discussed. Moreover, the shortcoming of UHF detection at metallic shielded GIS is identified and feasible solving through detection points at non-metallic secondary wiring terminals of Current Transformer (CT) and Voltage Transformer (VT) is described.
Keywords
current transformers; gas insulated switchgear; partial discharges; potential transformers; GIS; UHF detection; UHF signal emission; current transformer; gas insulated switchgear; nonmetallic secondary wiring terminals; partial discharge detection; voltage 132 kV; voltage 400 kV; voltage transformer; Couplers; Detectors; Gas insulation; Handheld computers; Partial discharges; Sensitivity; Wiring; Condition monitoring; Gas insulation; Highvoltage techniques; Partial discharges; Switchgear; UHF measurements;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2013 IEEE PES Asia-Pacific
Conference_Location
Kowloon
Type
conf
DOI
10.1109/APPEEC.2013.6837317