Using IEC 61850 process bus to meet NERC PRC-005-2 Condition Based Maintenance requirements
Author
Hunt, Rich ; Ernst, Tom
Author_Institution
GE Digital Energy, Apex, NC, USA
fYear
2015
fDate
March 30 2015-April 2 2015
Firstpage
546
Lastpage
552
Abstract
Process bus uses distributed merging units to sample analog measurements such as currents and voltages. The use of redundant merging units allows relays to continuously monitor the performance of the merging units by comparing the values from each. This continuous monitoring meets NERC PRC-005-2 Condition Based Maintenance requirements, and eliminates the need for routine testing of protective relay analog circuits.
Keywords
automatic testing; maintenance engineering; power system protection; IEC 61850 process bus; NERC PRC-005-2 condition based maintenance requirements; analog measurements; distributed merging units; protective relay analog circuits; Current measurement; Maintenance engineering; Merging; Microprocessors; Monitoring; Relays; Testing; Power system protection; automatic testing; system testing;