• DocumentCode
    715157
  • Title

    Distribution network topology detection with time-series measurements

  • Author

    Cavraro, G. ; Arghandeh, R. ; Barchi, G. ; von Meier, A.

  • Author_Institution
    DEI, Univ. of Padova, Padua, Italy
  • fYear
    2015
  • fDate
    18-20 Feb. 2015
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper proposes a novel approach to detecting the topology of distribution networks based on the analysis of time series measurements. The analysis approach draws on data from high-precision phasor measurement units (PMUs or synchrophasors) for distribution systems. A key fact is that time-series data taken from a dynamic system show specific patterns regarding state transitions such as opening or closing switches, as a kind of signature from each topology change. The algorithm proposed here is based on the comparison of the actual signature of a recent state transition against a library of signatures derived from topology simulations. The IEEE 33-bus model is used for initial algorithm validation.
  • Keywords
    busbars; distribution networks; network topology; phasor measurement; time series; IEEE 33-bus model; PMU; distribution network topology detection; high-precision phasor measurement unit; state transition; time-series measurement; Market research; Network topology; Noise measurement; Phasor measurement units; Switches; Topology; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Innovative Smart Grid Technologies Conference (ISGT), 2015 IEEE Power & Energy Society
  • Conference_Location
    Washington, DC
  • Type

    conf

  • DOI
    10.1109/ISGT.2015.7131897
  • Filename
    7131897