DocumentCode :
717274
Title :
Comparison of the transient performance of STATCOM and Synchronous condenser at HVDC converter stations
Author :
Yi Zhang ; Gole, Aniruddha M.
Author_Institution :
RTDS Technol. Inc., Winnipeg, MB, Canada
fYear :
2015
fDate :
10-12 Feb. 2015
Firstpage :
1
Lastpage :
8
Abstract :
This paper compared the transient performance of Synchronous Condenser and Static Compensator (STATCOM) at HVDC systems. The impacts of the two reactive power compensators to the connected HVDC system during various aspects of transients, including fault recovery, temporary over voltage and commutation failure, are investigated based on Electromagnetic Transients (EMT) Simulation. The study results demonstrated that STATCOMs and SCs have the similar performance during those transients.
Keywords :
EMTP; HVDC power convertors; overvoltage; power capacitors; static VAr compensators; EMT simulation; HVDC converter stations; STATCOM; commutation failure; electromagnetic transients simulation; fault recovery; reactive power compensators; synchronous condenser and static compensator; temporary over voltage; HVDC; STATCOM; Synchronous Condenser; Transient Performance;