• DocumentCode
    720335
  • Title

    A communication assisted solution for a 138kV distance relay misoperation

  • Author

    Turner, Christopher L. ; Ranganathan, Prakash

  • Author_Institution
    Dept. of Electr. Eng., Univ. of North Dakota, Grand Forks, ND, USA
  • fYear
    2015
  • fDate
    7-10 June 2015
  • Firstpage
    193
  • Lastpage
    198
  • Abstract
    This paper discuss a 138 kV miss operation due to a zone 1 overreach of a microprocessor relay. A communication assisted solution to the overreach without compromising the security of the line has been presented that will also increase the dependability of the line.
  • Keywords
    current transformers; microprocessor chips; power engineering computing; power transformer protection; relay protection; communication assisted solution; current transformer; distance relay misoperation; line security; microprocessor relay; voltage 138 kV; Current transformers; Power transmission lines; Programming; Relays; Security; Substations; Testing; Breakers; Current Transformers; Fault;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    DC Microgrids (ICDCM), 2015 IEEE First International Conference on
  • Conference_Location
    Atlanta, GA
  • Type

    conf

  • DOI
    10.1109/ICDCM.2015.7152037
  • Filename