    Basic consideration of winding arrangement of amorphous transformers for MW-class DC-DC converters

  • Author

    Tanaka, H. ; Nakamura, K. ; Ichinokura, O.

  • Author_Institution
    Tohoku Univ., Sendai, Japan
  • fYear
    2015
  • fDate
    11-15 May 2015
  • Firstpage
    1
  • Lastpage
    1
  • Abstract
    An interleaved winding arrangement is examined in this article for use in MW-class DC-DC converters. The frequency dependences of winding resistance of interleaved and non-interleaved winding arrangements are compared experimentally using a 10-kW test amorphous transformer. It is demonstrated that copper loss of non-interleaved winding significantly increases although the operating frequency is below 1 kHz. Hence, the MW-class amorphous transformer requires an interleaved winding to reduce copper loss.
  • Keywords
    DC-DC power convertors; power transformers; transformer windings; DC-DC converters; amorphous transformers; copper loss; frequency dependences; interleaved winding arrangement; power 10 kW; winding resistance; Copper; DC-DC power converters; Electrical resistance measurement; Frequency dependence; Resistance; Transformer cores; Windings;