DocumentCode :
722015
Title :
Remanence detection and low-frequency degaussing for power transformers based on modified J-A model
Author :
Li, J. ; Li, Z. ; Zhong, X. ; Li, T. ; Gu, Y. ; Zhao, Z. ; Jiang, W. ; Raza, S.A.
Author_Institution :
High Voltage & Insulation Inst., Xi´an Jiaotong Univ., Xi´an, China
fYear :
2015
fDate :
11-15 May 2015
Firstpage :
1
Lastpage :
1
Abstract :
In this paper, based on the modified Jiles-Atherton model, the effects of eddy current and temperature were taken into account to study the hysteresis characteristic of any point on B-H loops. Then, as long as the initial demagnetization point is known from voltage and current waveforms in practice, the terminal of demagnetization, or the residual flux, can be determined. A low-frequency degaussing method is introduced to reduce the source power, but it´ll take more time when compared with the degaussing under the normal frequency. Accordingly, the multi objective programming approach was adopted to determine an optimal frequency trading off between power demands and degaussing time. What´s more, to assess the effectiveness of both residual flux measuring and degaussing methods, an experiment platform was built eventually.
Keywords :
demagnetisation; eddy currents; magnetic flux; magnetic hysteresis; power transformers; remanence; B-H loops; current waveforms; eddy current; hysteresis characteristic; initial demagnetization point; low-frequency degaussing; modified Jiles-Atherton model; multi objective programming approach; power transformers; remanence detection; residual flux; temperature effects; Analytical models; Circuit faults; Demagnetization; Power transformers; Surge protection; Surges; Time-frequency analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Magnetics Conference (INTERMAG), 2015 IEEE
Conference_Location :
Beijing
Print_ISBN :
978-1-4799-7321-7
Type :
conf
DOI :
10.1109/INTMAG.2015.7157295
Filename :
7157295
Link To Document :
بازگشت