DocumentCode
72506
Title
Calculation of the Phase-Angle-Jump for Voltage Dips in Three-Phase Systems
Author
Ying Wang ; Bollen, Math H. J. ; Xian-Yong Xiao
Author_Institution
Coll. of Electr. Eng. & Inf. Technol., Sichuan Univ., Chengdu, China
Volume
30
Issue
1
fYear
2015
fDate
Feb. 2015
Firstpage
480
Lastpage
487
Abstract
The phase-angle-jump is defined in this paper as another single-event characteristic of voltage dips, besides residual or characteristic voltage and duration. This paper proposes and compares six methods to calculate the phase-angle-jump for measured voltage dips in a three-phase system. This paper also studies the details of the calculation: correcting frequency and transition segments. The six proposed methods have been applied to 235 sets of measured voltage dips and a statistical comparison has been made. It is recommended that two of the methods be included in IEEE Standard 1564 and IEC 61000-4-30.
Keywords
IEC standards; IEEE standards; power supply quality; power system faults; statistical analysis; IEC 61000-4-30 standard; IEEE standard 1564; correcting frequency; phase-angle-jump calculation; power quality; statistical comparison; three-phase power system fault; transition segment; voltage dip; IEC standards; IEEE standards; Phase measurement; Time-frequency analysis; Voltage fluctuations; Voltage measurement; PQ indices; Power quality (PQ); power system faults; power transmission and distribution; voltage dips;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2014.2352358