Abstract
Synchrophasors are increasingly being implemented to improve the understanding of network performance. This paper presents the use of voltage and current synchrophasors in the on-line performance monitoring of a transmission line. Line parameters, conductor temperature and sag are continuously derived. Power transfer capability and voltage stability requires minimal additional computational effort. The system operator can continuously access the real state of the power system and not estimated values obtained from state estimators if both voltage and current synchrophasor data is available. Field data obtained across a 330kV, 521 km line is used to evaluate these opportunities.
Keywords
phasor measurement; power system stability; transmission networks; online performance monitoring; power transfer capability; synchrophasor measurements; transmission line monitoring; voltage stability; Conductors; Monitoring; Power system stability; Power transmission lines; Resistance; Transmission line measurements; Voltage measurement; Power system stability; Synchrophasor applications; Transmission line modeling; Transmission line parameter estimation;
fLanguage
English
Publisher
ieee
Conference_Titel
PowerTech, 2015 IEEE Eindhoven
Conference_Location
Eindhoven
Type
conf
DOI
10.1109/PTC.2015.7232541
Filename
7232541
Link To Document