Title :
Switching impulse breakdown characteristics of large sphere-plane air gaps compared with rod-plane air gap
Author :
She Chen ; Rong Zeng ; Chijie Zhuang ; Zhanqing Yu ; Jinliang He
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Abstract :
With the increase of operation voltage to 800 kV-1100 kV, the sphere-plane gaps with radius of 0.5-1 meter are widely used in the converter station of UHVDC power transmission system. In order to ensure the safety of UHVDC system and reduce the investment, it is necessary to investigate the breakdown characteristic of large radius sphere-plane gap. This paper implemented experiments on three different gap configurations: rod-plane, sphere (R=0.55 m)-plane, and sphere (R=0.75 m)-plane. The 50% breakdown voltages and the current injected into the high voltage electrode were measured. Besides, the discharge process was observed by a high speed CCD camera. Three types of current waveforms related to different streamer progression characteristics were found. With the increase of sphere radius, it can be found that the streamer gradually becomes dominant in the discharge process, which leads to higher average breakdown field, longer streamer length and much more injected charge of first streamer.
Keywords :
CCD image sensors; HVDC power transmission; air gaps; discharges (electric); power convertors; UHVDC power transmission system; breakdown voltages; converter station; current injection; discharge process; high speed CCD camera; high voltage electrode; investment reduction; large sphere-plane air gaps; rod-plane air gap; size 0.5 m to 1 m; streamer progression characteristics; switching impulse breakdown characteristics; voltage 800 kV to 1100 kV; Cameras; Current measurement; Discharges (electric); Electrodes; Switches; Voltage measurement; Large radius sphere-plane gap; high speed camera; pre-breakdown current; streamer; switching impulse;
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
DOI :
10.1109/TDEI.2013.6518953