DocumentCode :
740909
Title :
Stability Enhancement of a Power System With a PMSG-Based and a DFIG-Based Offshore Wind Farm Using a SVC With an Adaptive-Network-Based Fuzzy Inference System
Author :
Li Wang ; Dinh-Nhon Truong
Author_Institution :
Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
Volume :
60
Issue :
7
fYear :
2013
fDate :
7/1/2013 12:00:00 AM
Firstpage :
2799
Lastpage :
2807
Abstract :
This paper presents the stability-improvement results of a synchronous generator (SG)-based one-machine infinite-bus system with a permanent-magnet SG (PMSG)-based offshore wind farm (OWF) and a doubly fed induction generator (DFIG)-based OWF using a static VAR compensator (SVC). The operating characteristics of the studied two OWFs are simulated by an equivalent aggregated PMSG driven by an equivalent wind turbine (WT) and an equivalent aggregated DFIG driven by an equivalent WT through an equivalent gearbox, respectively. A damping controller of the SVC is designed by using adaptive-network-based fuzzy inference system (ANFIS) to contribute adequate damping characteristics to the dominant modes of the studied SG under various operating conditions. A frequency-domain approach based on a linearized system model using root-loci technique and a time-domain scheme based on a nonlinear system model subject to various disturbances are both utilized to examine the effectiveness of the proposed control scheme. It can be concluded from the simulation results that the proposed SVC joined with the ANFIS damping controller is capable of improving the stability of the studied SG system subject to different disturbances.
Keywords :
asynchronous generators; fuzzy reasoning; machine control; nonlinear control systems; offshore installations; permanent magnet generators; power generation control; power system stability; root loci; static VAr compensators; synchronous generators; time-domain analysis; wind power plants; wind turbines; ANFIS damping controller; DFIG-based offshore wind farm; OWF; PMSG-based offshore wind farm; SVC; WT; adaptive-network-based fuzzy inference system; damping characteristics; equivalent gearbox; equivalent wind turbine; frequency-domain approach; linearized system model; nonlinear system model; one-machine infinite-bus system; permanent-magnet synchronous generator; power system stability enhancement; root-loci technique; static VAR compensator; time-domain scheme; Damping; Fuzzy logic; Power system stability; Stability analysis; Static VAr compensators; Voltage control; Wind speed; Doubly fed induction generator (DFIG); offshore wind farm (OWF); permanent-magnet synchronous generator (PMSG); stability; static VAR compensator (SVC);
fLanguage :
English
Journal_Title :
Industrial Electronics, IEEE Transactions on
Publisher :
ieee
ISSN :
0278-0046
Type :
jour
DOI :
10.1109/TIE.2012.2218557
Filename :
6313906
Link To Document :
بازگشت