Title :
Time-Domain Fault-Location Method on HVDC Transmission Lines Under Unsynchronized Two-End Measurement and Uncertain Line Parameters
Author :
Liang Yuansheng ; Wang Gang ; Li Haifeng
Author_Institution :
Sch. of Electr. Power Eng., South China Univ. of Technol., Guangzhou, China
Volume :
30
Issue :
3
fYear :
2015
fDate :
6/1/2015 12:00:00 AM
Firstpage :
1031
Lastpage :
1038
Abstract :
This paper presents a novel time-domain fault location algorithm on HVDC transmission lines. The Bergeron line model is adopted to construct a time-domain fault location equation, considering unsynchronized two-end measurement and uncertain line parameters. The zero time reference point is set to the sample point of arrival at each end for the traveling wave-head. Time-tags of all sample points change with the zero time reference. So the time difference of two-end measurements has changed also, and equals the time difference between arrivals at two ends for the traveling wave-head. That makes it possible to mix the traveling wave theory with the Bergeron time-domain fault location method. Besides, the ratio coefficient of wave velocities between different frequencies and digital band-pass filter are presented for better performance of the proposed method. Simulations and tests demonstrate that the proposed method can locate faults accurately on the HVDC lines even in the case of loss of signals from GPS.
Keywords :
HVDC power transmission; fault location; power transmission faults; time-domain analysis; transmission network calculations; Bergeron line model; GPS; HVDC transmission lines; digital band pass filter; time domain fault location algorithm; time domain fault location equation; time domain fault location method; uncertain line parameters; unsynchronized two end measurement; unsynchronized two-end measurement; zero time reference point; Equations; HVDC transmission; Mathematical model; Time measurement; Time-domain analysis; Transmission line measurements; Voltage measurement; Fault location; HVDC transmission lines; time-domain method; traveling wave; unsynchronized two-end measurement;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2014.2335748