DocumentCode
747432
Title
Precision measurement of power harmonics and flicker
Author
Budovsky, Ilya ; Hammond, Greg
Author_Institution
Nat. Meas. Inst., Lindfield, NSW, Australia
Volume
54
Issue
2
fYear
2005
fDate
4/1/2005 12:00:00 AM
Firstpage
483
Lastpage
487
Abstract
This paper describes a precision measurement system developed at the National Measurement Institute Australia (NMIA) for the calibration of three-phase instruments measuring harmonics of current up to 20 A, voltage fluctuation, and flicker. Particular attention is given to establishing a traceable link to the Australian primary standards of electrical quantities. Current and voltage harmonics up to the ninety-ninth and fluctuating voltages can be generated and measured with relative uncertainties close to 1×10-5 of the fundamental.
Keywords
electric variables measurement; electromagnetic compatibility; flicker noise; fluctuations; measurement standards; power system harmonics; power system measurement; National Measurement Institute Australia; current harmonics; electrical quantities; electromagnetic capability; fluctuating voltages; measurement standards; power flicker; power harmonics; precision measurement; voltage fluctuation; voltage harmonics; Australia; Calibration; Current measurement; Digital systems; Electromagnetic compatibility; Electromagnetic measurements; IEC standards; Power measurement; Power system harmonics; Voltage fluctuations; Electromagnetic capability (EMC); flicker; harmonics; standards;
fLanguage
English
Journal_Title
Instrumentation and Measurement, IEEE Transactions on
Publisher
ieee
ISSN
0018-9456
Type
jour
DOI
10.1109/TIM.2004.843313
Filename
1408215
Link To Document