    Discussion of "Active voltage correction for industrial plants"

  • Author

    Barros, Julio

  • Author_Institution
    Dept. of Electron. & Comput., Univ. of Cantabria, Santander, Spain
  • Volume
    39
  • Issue
    4
  • fYear
    2003
  • Firstpage
    1211
  • Abstract
    The author comments on the paper by D. Ezer et al. (see ibid., vol.38, p.1641-6, 2002), briefly reviewing the proposals put forward. The author discusses the proposal to use active voltage conditioners (AVCs) as a solution to mitigate the effect of voltage sags in industrial plants, pointing out that this seems to be effective for the case studies mentioned but not, in his opinion, for a general case. The author also points out an apsect not considered in the paper which is the synchronization of the additive voltage injected by the series transformer with the voltage supply in the distribution system in order to mitigate phase jumps.
  • Keywords
    distribution networks; industrial plants; industrial power systems; invertors; active voltage conditioners; active voltage correction; additive voltage injection; distribution system; industrial plants; inverters; phase jumps mitigation; series transformer; voltage sags mitigation; voltage supply; Electronic equipment; Energy storage; Harmonic distortion; Industrial plants; Microcomputers; Power quality; Power system harmonics; Programmable control; Protection; Voltage fluctuations;