• DocumentCode
    750877
  • Title

    Partial discharge signal generation transmission and acquisition

  • Author

    Fruth, B.A. ; Gross, D.W.

  • Author_Institution
    Power Diagnostix GmbH, Aachen, Germany
  • Volume
    142
  • Issue
    1
  • fYear
    1995
  • fDate
    1/1/1995 12:00:00 AM
  • Firstpage
    22
  • Lastpage
    28
  • Abstract
    The phase resolved partial discharge detection technique (or `PD pattern recording technique´) is applicable to field measurements, particularly if combined with disturbance rejection techniques and non-conventional pick-up circuits. Electromagnetic disturbances can be eliminated by filtering in the time domain (impulse noise gating) and/or in the frequency domain (down-mixing). The PD patterns not only reveal the PD physics and thus help to identify the defect type, but also serve to evaluate the efficiency of the disturbance rejection procedure
  • Keywords
    ageing; charge measurement; data acquisition; frequency-domain analysis; insulation testing; partial discharges; signal processing; time-domain analysis; disturbance rejection procedure; disturbance rejection techniques; down-mixing; efficiency evaluation; electromagnetic disturbances; field measurements; filtering; frequency domain; impulse noise gating; phase resolved partial discharge detection; pick-up circuits; time domain;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:19951643
  • Filename
    370776