DocumentCode
750877
Title
Partial discharge signal generation transmission and acquisition
Author
Fruth, B.A. ; Gross, D.W.
Author_Institution
Power Diagnostix GmbH, Aachen, Germany
Volume
142
Issue
1
fYear
1995
fDate
1/1/1995 12:00:00 AM
Firstpage
22
Lastpage
28
Abstract
The phase resolved partial discharge detection technique (or `PD pattern recording technique´) is applicable to field measurements, particularly if combined with disturbance rejection techniques and non-conventional pick-up circuits. Electromagnetic disturbances can be eliminated by filtering in the time domain (impulse noise gating) and/or in the frequency domain (down-mixing). The PD patterns not only reveal the PD physics and thus help to identify the defect type, but also serve to evaluate the efficiency of the disturbance rejection procedure
Keywords
ageing; charge measurement; data acquisition; frequency-domain analysis; insulation testing; partial discharges; signal processing; time-domain analysis; disturbance rejection procedure; disturbance rejection techniques; down-mixing; efficiency evaluation; electromagnetic disturbances; field measurements; filtering; frequency domain; impulse noise gating; phase resolved partial discharge detection; pick-up circuits; time domain;
fLanguage
English
Journal_Title
Science, Measurement and Technology, IEE Proceedings -
Publisher
iet
ISSN
1350-2344
Type
jour
DOI
10.1049/ip-smt:19951643
Filename
370776
Link To Document