Title :
An advanced method for testing of distance relay operating characteristic
Author :
Kezunovic, M. ; Xia, Y.Q. ; Guo, Y. ; Fromen, C.W. ; Sevcik, D.R.
Author_Institution :
Texas A&M Univ., College Station, TX, USA
fDate :
1/1/1996 12:00:00 AM
Abstract :
This paper describes a test method for distance relays using an advanced open-loop digital simulator. Derivation of test signals during prefault and fault, and test procedure are introduced. It is demonstrated that the method of generating test signals and the procedure of applying them to a relay under test directly affect test results. Prefault voltage and current are also a very important factor. The decaying DC offset is considered as well. Test results for five different relays using this new method are presented in this paper. The results demonstrate practical benefits of the test method
Keywords :
digital simulation; power system analysis computing; power system protection; relay protection; testing; decaying DC offset; distance relay operating characteristic; distance relay testing; fault; open-loop digital simulator; phasor quantities; prefault; test procedure; test signals generation; Computational modeling; Digital relays; Impedance; Polarization; Power system relaying; Protective relaying; Senior members; Steady-state; Testing; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on