Observation and analysis of multiple-phase grounding faults caused by lightning
Author :
Inoue, Atsuyuki ; Kanao, Sei-ichi
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume :
11
Issue :
1
fYear :
1996
fDate :
1/1/1996 12:00:00 AM
Firstpage :
353
Lastpage :
360
Abstract :
This paper describes four phase and five-phase grounding faults caused by lightning on a 154-kV overhead transmission line. The authors measured insulator voltages and currents flowing along the ground wire and the tower. In addition, they photographed lightning strokes to the transmission line and flashovers between the arcing horns and examined the fault phases at substations. The paper analyzes insulator voltage waveforms using the Electromagnetic Transients Program (EMTP) and estimates the fault processes
Keywords :
earthing; electric current measurement; lightning protection; poles and towers; power overhead lines; power system analysis computing; power system measurement; power system protection; software packages; voltage measurement; 154 kV; EMTP; Electromagnetic Transients Program; arcing horns; computer simulation; fault processes; five-phase; flashovers; four-phase; ground wires; grounding faults; insulator current measurement; insulator voltage measurement; lightning; multiple-phase grounding faults; overhead power transmission line; substations; towers; voltage waveforms; Cable insulation; Current measurement; EMTP; Electromagnetic measurements; Grounding; Lightning; Power transmission lines; Transmission line measurements; Voltage; Wire;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.484035
Filename :
484035
Link To Document :
بازگشت