• DocumentCode
    751900
  • Title

    Observation and analysis of multiple-phase grounding faults caused by lightning

  • Author

    Inoue, Atsuyuki ; Kanao, Sei-ichi

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    11
  • Issue
    1
  • fYear
    1996
  • fDate
    1/1/1996 12:00:00 AM
  • Firstpage
    353
  • Lastpage
    360
  • Abstract
    This paper describes four phase and five-phase grounding faults caused by lightning on a 154-kV overhead transmission line. The authors measured insulator voltages and currents flowing along the ground wire and the tower. In addition, they photographed lightning strokes to the transmission line and flashovers between the arcing horns and examined the fault phases at substations. The paper analyzes insulator voltage waveforms using the Electromagnetic Transients Program (EMTP) and estimates the fault processes
  • Keywords
    earthing; electric current measurement; lightning protection; poles and towers; power overhead lines; power system analysis computing; power system measurement; power system protection; software packages; voltage measurement; 154 kV; EMTP; Electromagnetic Transients Program; arcing horns; computer simulation; fault processes; five-phase; flashovers; four-phase; ground wires; grounding faults; insulator current measurement; insulator voltage measurement; lightning; multiple-phase grounding faults; overhead power transmission line; substations; towers; voltage waveforms; Cable insulation; Current measurement; EMTP; Electromagnetic measurements; Grounding; Lightning; Power transmission lines; Transmission line measurements; Voltage; Wire;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.484035
  • Filename
    484035