DocumentCode :
758731
Title :
Decreasing grounding resistance of substation by deep-ground-well method
Author :
He, Jinliang ; Yu, Gang ; Yuan, Jingping ; Zeng, Rong ; Zhang, Bo ; Zou, Jun ; Guan, Zhicheng
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume :
20
Issue :
2
fYear :
2005
fDate :
4/1/2005 12:00:00 AM
Firstpage :
738
Lastpage :
744
Abstract :
Grounding system is very important to maintain the safe and reliable operation of power network and ensure the safety of power apparatus and operators. A new technique to decrease grounding resistance of substation is presented in this paper, which makes use of deep ground well to decrease the grounding resistance. The ground well is formed by metal tube with water percolation apertures in the soil with groundwater, which has the ability to gather the groundwater and wet the surrounding soil. The principle of deep ground well to decrease grounding resistance is to decrease the resistivity of the soil region surrounding the grounding well by leading the groundwater moving to the deep ground well under pressure, and consequently decrease the grounding resistance of the deep ground well. This novel method was applied in a substation grounding engineering, and good effect was achieved.
Keywords :
earthing; substation protection; deep-ground-well method; grounding resistance; groundwater; power network reliable operation; power network safe operation; substation; Conductivity; Electrodes; Grounding; Helium; Immune system; Power system faults; Power system reliability; Safety; Soil; Substations; Deep ground well; grounding electrode; grounding resistance; grounding system; soil resistivity; substation;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2005.844301
Filename :
1413310
Link To Document :
بازگشت