• DocumentCode
    759605
  • Title

    The ultra-saturation phenomenon of loaded transformer energization and its impacts on differential protection

  • Author

    Lin, Xiang-ning ; Liu, Pei

  • Author_Institution
    Huazhong Univ. of Sci. & Technol., Wuhan, China
  • Volume
    20
  • Issue
    2
  • fYear
    2005
  • fDate
    4/1/2005 12:00:00 AM
  • Firstpage
    1265
  • Lastpage
    1272
  • Abstract
    A sort of unusual maloperation of the differential protection of the transformer and delayed maloperations due to the loaded transformer energization are reported. A second-order equivalent circuit-based model is set up to investigate this phenomenon. With rational assumptions and simplifications, the analytical solution of the main flux of the transformer is obtained. On the basis of the expression of the flux, the delayed maloperation can be explained in a rational way. Furthermore, a peculiar transient phenomenon of transformer energization, specified as "ultra-saturation" in this paper, is revealed. It was substantiated to be a more severely adverse condition in terms of the security of the transformer differential protection. In the extreme case, all existing blocking schemes implemented with the identification of the characteristics of inrushes or fluxes will be of no effect regardless of how to set the threshold. A variety of the simulation tests proves that the delayed maloperation of the differential protection and ultra-saturation of the transformer core may occur in the occasion of loaded transformer energization.
  • Keywords
    power system protection; transformer protection; transient analysis; blocking schemes; differential protection; loaded transformer energization; main flux; maloperation; second-order equivalent circuit-based model; transient phenomenon; ultra-saturation phenomenon; Circuit faults; Delay; Magnetic flux; Power transformers; Protective relaying; Security; Substation protection; Surge protection; Testing; Transformer cores; Delayed maloperation; differential protection of transformer; energization of loaded transformer; transient; ultra-saturation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2004.833919
  • Filename
    1413389