DocumentCode
760057
Title
Experimental study of current-dependent grounding resistance of rod electrode
Author
Sekioka, Shozo ; Sonoda, Toshio ; Ametani, Akihiro
Author_Institution
Kansai Tech Corp., Osaka, Japan
Volume
20
Issue
2
fYear
2005
fDate
4/1/2005 12:00:00 AM
Firstpage
1569
Lastpage
1576
Abstract
This paper has experimentally investigated transient behavior of grounding electrode systems especially for a high impulse current up to 40 kA in particular reference with a mutual grounding resistance between the electrodes. The experimental results show that the mutual grounding resistance depends on the applied current similarly to the current dependence of the self-grounding resistance. The phenomenon can be explained by the increase of an effective rod radius and an effective length. The self-grounding resistance greatly depends on the rod dimension and on the soil resistivity for low currents as analytically well known. However, the parameters cause a less effect on the nonlinear characteristic for high currents exceeding 10 kA.
Keywords
earth electrodes; electric resistance; transient analysis; current-dependent grounding resistance; effective length; effective radius; grounding electrode systems; mutual grounding resistance; rod dimension; rod electrode; soil resistivity; transient behavior; Conductivity; Current measurement; Electric resistance; Electrical resistance measurement; Electrodes; Grounding; Ionization; Lightning; Soil measurements; Surges; Current dependence; grounding resistance; lightning surge; soil ionization;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2004.838660