• DocumentCode
    760057
  • Title

    Experimental study of current-dependent grounding resistance of rod electrode

  • Author

    Sekioka, Shozo ; Sonoda, Toshio ; Ametani, Akihiro

  • Author_Institution
    Kansai Tech Corp., Osaka, Japan
  • Volume
    20
  • Issue
    2
  • fYear
    2005
  • fDate
    4/1/2005 12:00:00 AM
  • Firstpage
    1569
  • Lastpage
    1576
  • Abstract
    This paper has experimentally investigated transient behavior of grounding electrode systems especially for a high impulse current up to 40 kA in particular reference with a mutual grounding resistance between the electrodes. The experimental results show that the mutual grounding resistance depends on the applied current similarly to the current dependence of the self-grounding resistance. The phenomenon can be explained by the increase of an effective rod radius and an effective length. The self-grounding resistance greatly depends on the rod dimension and on the soil resistivity for low currents as analytically well known. However, the parameters cause a less effect on the nonlinear characteristic for high currents exceeding 10 kA.
  • Keywords
    earth electrodes; electric resistance; transient analysis; current-dependent grounding resistance; effective length; effective radius; grounding electrode systems; mutual grounding resistance; rod dimension; rod electrode; soil resistivity; transient behavior; Conductivity; Current measurement; Electric resistance; Electrical resistance measurement; Electrodes; Grounding; Ionization; Lightning; Soil measurements; Surges; Current dependence; grounding resistance; lightning surge; soil ionization;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2004.838660
  • Filename
    1413427