• DocumentCode
    760349
  • Title

    Harmonic domain characterization of the resonant interaction between generator and transmission line

  • Author

    Ramirez, Abner ; Semlyen, Adam ; Iravani, Reza

  • Author_Institution
    CINVESTAV-Guadalajara, Jalisco, Mexico
  • Volume
    20
  • Issue
    2
  • fYear
    2005
  • fDate
    4/1/2005 12:00:00 AM
  • Firstpage
    1753
  • Lastpage
    1762
  • Abstract
    It is known that an untransposed open-ended line causes a negative sequence component in the current and the generator reacts through third and higher harmonic voltages. The currents and voltages can be greatly amplified by resonance to any of these harmonics. The phenomenon of machine-line interaction has traditionally been explained as a sequence of interactive events between the line and the machine. This paper presents a unified noniterative mathematical representation of this interaction. The analysis is formulated in the harmonic domain abc-frame to detect resonance conditions and for the assessment of their stability.
  • Keywords
    harmonic analysis; power system harmonics; power transmission lines; synchronous generators; abc-frame; generator-transmission line interaction; harmonic domain characterization; higher harmonic voltages; machine-line interaction; negative sequence component; noniterative mathematical representation; resonant interaction; third harmonic voltages; untransposed open-ended line; Character generation; Frequency; Harmonic analysis; Power transmission lines; Resonance; Time varying systems; Transmission line matrix methods; Transmission line theory; Transmission lines; Voltage; Harmonic domain; harmonics; resonance; standing waves; state space methods; time-periodic systems; time-varying systems; unbalanced transmission line;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2004.834678
  • Filename