DocumentCode
762004
Title
Protective relaying an medium- and high-voltage system
Author
Dudor, Joseph S. ; Padden, Larraine K.
Author_Institution
Midway City, CA, USA
Volume
2
Issue
2
fYear
1996
Firstpage
27
Lastpage
34
Abstract
For this article we reviewed unusual outages, such as nonselective device operations during a fault, at different petroleum industry facilities. We found that changing some types of protective devices and modifying device settings improved both reliability and on-line performance. The following categories of protection problems were reviewed: ground faults on 12 kV feeders; ground faults on 4 kV motor feeders; faults on 115 kV transmission lines; and overexcitation of equipment. Each case is presented with: a brief synopsis of the problem encountered; our evaluation of the problem, including suggested solutions; and the “lessons to be learned” and trouble spots to avoid
Keywords
earthing; electrical faults; petroleum industry; power system protection; power system relaying; relay protection; 115 kV; 12 kV; 4 kV; device settings modification; equipment overexcitation; ground faults; high-voltage system; medium-voltage system; motor feeders; nonselective device operations; on-line performance; petroleum industry facilities; protective relaying; reliability; transmission lines; unusual outages; Circuit breakers; Circuit faults; Current transformers; Fuses; Grounding; Production systems; Protection; Protective relaying; Relays; Resistors;
fLanguage
English
Journal_Title
Industry Applications Magazine, IEEE
Publisher
ieee
ISSN
1077-2618
Type
jour
DOI
10.1109/2943.485760
Filename
485760
Link To Document