Abstract :
A unique method is presented which determines the bus voltage and angle at post-outage steady state, using an improved linearised load-flow method and the sensitivity relationship of the power system. This proposed noniterative method has been applied to 14- and 30-bus IEEE test systems. The results obtained are compared with the NR load-flow and the FDLF-compensation method, to show the effectiveness of this method
Keywords :
busbars; load flow; power systems; 14 bus IEEE system; 30 bus IEEE system; FDLF-compensation method; NR load-flow; bus voltage; fast decoupled load flow; line outage contingency evaluation; linearised load-flow method; noniterative method; post-outage steady state; power system; sensitivity relationship;