DocumentCode :
766602
Title :
Optimal PID gain schedule for hydrogenerators-design and application
Author :
Orelind, G. ; Wozniak, L. ; Medanic, J. ; Whittemore, T.
Author_Institution :
Adept Technol., San Jose, CA, USA
Volume :
4
Issue :
3
fYear :
1989
fDate :
9/1/1989 12:00:00 AM
Firstpage :
300
Lastpage :
307
Abstract :
The development and testing of a digital gain switching governor for hydrogenerators are described. Optimal gains are found at different load points by minimizing a quadratic performance criterion prior to controller operation. During operation, the gain sets are switched in depending on gate position and speed error magnitude. It is shown that, with gain switching operating, the digital governor has a substantial reduction of noise on the command signal and up to 42% faster responses to power requests. Nonlinear control strategies enable the digital governor to have a 2.5% to 2% reduction in speed overshoot on start-ups and an 8% to 1% reduction in undershoot on load rejections as compared to the analog
Keywords :
digital control; hydroelectric generators; optimal control; three-term control; controller operation; digital gain switching governor; hydrogenerators; load points; load rejections; nonlinear control; optimal PID gain; quadratic performance; speed error magnitude; speed overshoot; start-ups; Contracts; Design engineering; Digital control; Error correction; Hydraulic turbines; Noise reduction; Optimal control; Performance gain; Software testing; Velocity control;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.43228
Filename :
43228
Link To Document :