Breakdown electric field calculations of hot SF6 for high voltage circuit breaker applications
Author :
Yousfi, M. ; Robin-Jouan, Ph. ; Kanzari, Z.
Author_Institution :
CNRS, Univ. of Paul Sabatier, Toulouse, France
Volume :
12
Issue :
6
fYear :
2005
Firstpage :
1192
Lastpage :
1200
Abstract :
The critical reduced electric field strengths of hot SF6 corresponding to the dielectric recovery phase of a high voltage circuit breaker are calculated for a large temperature range (300-3000 K). Calculations are based on a multi-term Boltzmann equation solution using, in comparison to the literature works, improved cross section sets for the interactions of electrons with various SF6 dissociated products. The obtained critical electric fields show a reasonable agreement with the available data. These results are then used in hydrodynamics simulations which correctly predicts the circuit breaker behaviors observed in the case of a successful breaking test as well as in a failed one.
Keywords :
Boltzmann equation; SF6 insulation; circuit breakers; electric breakdown; 300 to 3000 K; SF6; breakdown voltage; collision cross section; dielectric recovery phase; electric field calculation; electron distribution function; gas temperature effect; high voltage circuit breaker; hot SF6; hydrodynamics simulation; multiterm Boltzmann equation; Boltzmann equation; Circuit breakers; Circuit testing; Dielectrics; Electric breakdown; Electrons; Hydrodynamics; Predictive models; Temperature distribution; Voltage;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2005.1561799
Filename :
1561799
Link To Document :
بازگشت