DocumentCode
771379
Title
An adaptive method for setting underfrequency load shedding relays
Author
Anderson, P.M. ; Mirheydar, M.
Author_Institution
Power Math Associates Inc., San Diego, CA, USA
Volume
7
Issue
2
fYear
1992
fDate
5/1/1992 12:00:00 AM
Firstpage
647
Lastpage
655
Abstract
An adaptive scheme is proposed for determining the amount of load to be shed by underfrequency relays based on the observed initial slope of the frequency deviation. following the system separation. This initial slope contains all the information required to estimate that size of the step change in load caused by the system separation and to forecast the depth and even the approximate time of the maximum frequency dip. From this observation, the first step of load shedding can be set up adaptively, with additional steps to follow at prescribed intervals and amounts. The first step is considered the most important and is selected arbitrarily at one-half the static load shed target, with additional increments of about 0.1 per unit to be shed at 0.3 Hz increments until the dynamic load shed amount has been reached
Keywords
load shedding; power system control; power system protection; relay protection; adaptive scheme; control; frequency deviation; frequency dip; power system protection; separation; underfrequency load shedding relays; Equations; Frequency conversion; Frequency estimation; Power system modeling; Power system relaying; Protection; Protective relaying; Relays; Time factors; Turbines;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.141770