• DocumentCode
    772059
  • Title

    Development of a method of partial discharge detection in extra-high voltage cross-linked polyethylene insulated cable lines

  • Author

    Katsuta, Ginzo ; Toya, Atsushi ; Muraoka, Keiichi ; Endoh, Takeshi ; Sekii, Yasuo ; Ikeda, Chuki

  • Author_Institution
    Tokyo Electric Power Co. Inc., Japan
  • Volume
    7
  • Issue
    3
  • fYear
    1992
  • fDate
    7/1/1992 12:00:00 AM
  • Firstpage
    1068
  • Lastpage
    1079
  • Abstract
    Deterioration in the insulation performance of extra-high voltage XLPE (cross-linked polyethylene) cables is believed to be attributable to the deterioration caused by partial discharges. After using an XLPE cable to investigate the behavior of partial discharges under various adverse conditions, the authors succeeded in developing a highly sensitive novel method of measuring partial discharge in XLPE cable lines. Partial discharges in a 275 kV XLPE cable live line have been measured using this method. As a result, a detection sensitivity of 1 pC has been achieved
  • Keywords
    cable insulation; organic insulating materials; partial discharges; power cables; 275 kV; EHV XLPE cables; deterioration; extra-high voltage cross-linked polyethylene insulated cable lines; partial discharge detection; Cable insulation; Cable shielding; Cables; Dielectrics and electrical insulation; Materials testing; Partial discharge measurement; Partial discharges; Polyethylene; Trees - insulation; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.141815
  • Filename
    141815