DocumentCode
772059
Title
Development of a method of partial discharge detection in extra-high voltage cross-linked polyethylene insulated cable lines
Author
Katsuta, Ginzo ; Toya, Atsushi ; Muraoka, Keiichi ; Endoh, Takeshi ; Sekii, Yasuo ; Ikeda, Chuki
Author_Institution
Tokyo Electric Power Co. Inc., Japan
Volume
7
Issue
3
fYear
1992
fDate
7/1/1992 12:00:00 AM
Firstpage
1068
Lastpage
1079
Abstract
Deterioration in the insulation performance of extra-high voltage XLPE (cross-linked polyethylene) cables is believed to be attributable to the deterioration caused by partial discharges. After using an XLPE cable to investigate the behavior of partial discharges under various adverse conditions, the authors succeeded in developing a highly sensitive novel method of measuring partial discharge in XLPE cable lines. Partial discharges in a 275 kV XLPE cable live line have been measured using this method. As a result, a detection sensitivity of 1 pC has been achieved
Keywords
cable insulation; organic insulating materials; partial discharges; power cables; 275 kV; EHV XLPE cables; deterioration; extra-high voltage cross-linked polyethylene insulated cable lines; partial discharge detection; Cable insulation; Cable shielding; Cables; Dielectrics and electrical insulation; Materials testing; Partial discharge measurement; Partial discharges; Polyethylene; Trees - insulation; Voltage;
fLanguage
English